Description

HMI E159715 I014762 0074 Touch Screen Panel Repair


E159715 I014762 0074 HMI Touchscreen Panel Glass Repair Kit

E159715 I014762 0074 Touch Screen Panel Glass IHM Highlights
• 12.1” TFT color display
• High brightness
• Sunlight-readable
• SVGA (800x600 pixel) resolution
• 64K colors
• Resistive touchscreen
• 10/100 Ethernet interface
• USB port
• Connection to industrial bus systems using optional plug-in modules
• Compatible with video input module
• 64 MB user memory
• Compatible with local I/O


The E159715 I014762 0074 HMI Panel Glass HMI is a state-of-the-art HMI device featuring a high-brightness sunlight-readable 12.1” TFT color display with SVGA (800x600) resolution and resistive touchscreen. E159715 I014762 0074 Touch Screen Panel Glass HMI has been specifically designed for use under extreme illumination conditions. Support for 64K colors in the brilliant TFT display will increase the realism of the images. The integrated 10/100 Ethernet interface enhances connectivity in complex control systems.





Specifications:

The table below describes the parameters of the E159715 I014762 0074 Touchscreen Panel.

Part Number: E159715 I014762 0074
Display Type: TFT LCD
Resolution: 800x600 pixel
Backlight: CCFL
Warranty: 365 Days
Input Power: 24VDC (+10%, -15%)
Operating Temperature: 0 to 45 °C
Display Size: 12.1 in
Touch screen: Resistive


FAQ:

Question: How to cleaning E159715 I014762 0074 Touch Panel Glass IHM faceplates?

Answer: The equipment must be cleaned only with a soft cloth and neutral soap product. Do not use solvents.


Question: What is E159715 I014762 0074 Touchscreen Calibration?

Answer:

  • Standard calibration:
  • 1. Recall Configuration Mode
  • 2. Touch the CLEAR key on the E159715 I014762 0074 screen until a small round symbol will appear on the top right corner of the screen
  • 3. touch and hold the symbol until it will move to the low left corner of the E159715 I014762 0074 screen
  • 4. touch and hold the symbol until the indication to touch the ← key will be displayed on the screen
  • 5. touch and hold the key ← until the indication to touch the ↓ key will be displayed on the screen
  • 6. touch and hold the key ↓ until the indication to touch the Enter key will be displayed on the screen
  • 7. touch and hold the Enter key until the panel will switch to Operation Mode (if a valid project is loaded in the memory)
  • Emergency calibration.
  • The Emergency calibration procedure should be used in all cases when it would result not possible to go to calibration using the standard procedure.
  • 1. Switch of the unit
  • 2. turn on the unit
  • 3. tap in the middle of the touchscreen with a frequency of about one second until the operator panel will enter the Calibration Mode
  • 4. perform the standard calibration procedure.