How to Replace the display module on Allen Bradly PanelView Plus 700 to 1500 Terminals

How to Replace the display module on Allen Bradly PanelView Plus 700 to 1500 Terminals

This section shows how to replace the display module on 700 to 1500
terminals. It is necessary to remove the communication module from
the logic module to perform this operation
Follow these steps to replace the display module.
1. Disconnect power from the terminal.
2. Remove the terminal from the panel.
3. Detach the communication module, if attached, from the logic
module by removing the four screws.
4. Loosen the six captive screws that attach the logic module to the
display module.
5. Carefully lift the logic module from the terminal.
6. Set the display module aside.
7. Position the new logic module over the new display module so
that the connectors align.
8. Push down on the logic module until firmly seated.
9. Tighten the six captive screws that secure the logic module to
the display module to a torque of 0.58 Nm ( 5…7 lb•in).
10. Attach the communication module (if necessary) and tighten the
four screws to a torque of 0.58 Nm (5…7 lb•in).